Chris Collins

Tools · electronics

AC circuits and phasors

Learn AC by playing with it — sine waves and rms; rotating phasors projected onto sines, a complex-number calculator and Euler's formula; R, L and C (ELI the ICE man), reactance and live impedance triangles; resonance, Q and the energy sloshing between L and C; power, power factor and correction; three-phase and the neutral current; transformers and the conjugate match — each with a randomised exercise to solve.

Added

Works with

How to use it

AC circuits are easiest to understand by watching them. Each tab takes one idea, shows it moving, explains it, and ends with a Solve this exercise whose values change every time — type your answers (engineering notation such as 4.7k, 100n or 416u works), Check, and Show working to see the method.

The animations run in slow motion — a quarter of a turn per second, whatever the frequency — while the numbers are the real ones. Pause animation (above the tabs) freezes them all; Speed changes the pace.

How to use it

  1. 1 · Sine waves — choose a sine, square or triangle and set its peak, frequency and phase; the plot marks the peak, peak-to-peak, rms and rectified average, and the table gives the form and crest factors. 230 V 50 Hz and 120 V 60 Hz load the mains. Below, add two sines: at the same frequency the sum is another sine (the phasors add head to tail, right); at different frequencies it beats.

  2. 2 · Phasors — an arrow spinning at ω, with its height traced out as a sine. Tick second phasor B and drag its phase to see lead and lag; show A + B adds them. The calculator below takes 3+4j, 3-j4, 5∠53.13 or 2←30 and adds, subtracts, multiplies or divides, with the working in both forms. Euler’s formula shows ejθ = cos θ + j sin θ on the unit circle.

  3. 3 · Impedance — ELI the ICE man: the voltage and current of a lone R, L or C. Then pick series or parallel RL, RC or RLC, type R, L and C, and drag the frequency: the reactance plot, the impedance (or admittance) triangle and the phasor diagram all follow. Go to f₀ jumps to resonance.

  4. 4 · Resonance — |Z| and the current against frequency for a series or parallel RLC, with f₀, Q, the bandwidth and the magnification (VC = Q·V in series), and the safety note that goes with it. Below, a charged capacitor rings into the inductor: watch the energy move between C and L and leak into R; raise R for critical and over-damping.

  5. 5 · Power — v, i and p = v·i for a load R + jX: the shaded areas are energy delivered and returned. The power triangle shows P, Q and S, and with a target power factor the capacitor that corrects it (dashed). Below: a three-phase capacitor bank in star and in delta, and what correction does — and does not — save on a bill.

  6. 6 · Three-phase — three phasors 120° apart with the line voltage √3 × phase at +30°. Load it in star with a neutral, star without one, or delta; set R and X per phase (or tick balanced). The current diagram lays Ia, Ib and Ic head to tail: balanced, they close and the neutral current is zero; unbalanced, the gap is IN — or, without a neutral, the star point shifts.

  7. 7 · Transformers — turns, primary voltage and a complex load give Vs, Is, Ip and the impedance the source sees, a²·ZL. Below, maximum power transfer: a map of load power over the RL–XL plane with the conjugate match marked, a slice through it, and the best pure resistor.

Settings and your exercise score are remembered in this browser.

Method and assumptions

  • Everything is linear and at a single frequency (sinusoidal steady state), except the ringing capacitor, which uses the exact solution of the series RLC for each damping regime. Phasors are rms unless shown as peak; the angle of an impedance is positive for inductive loads (current lagging).

  • Power factor is cos φ, the displacement power factor; distorted (non-sinusoidal) currents from rectifiers lower the true power factor further and put third-harmonic current in a neutral even when the load is balanced — outside this model.

  • The parallel RLC is ideal R ‖ L ‖ C, with Q = R√(C/L); a real inductor’s series resistance makes the formulas approximate at low Q. The ringdown for a parallel tank is drawn as the series loop with the same Q.

  • The transformer is ideal: no losses, no magnetising current, perfect coupling.

  • The bill model is illustrative: a kVA maximum-demand charge, a reactive-energy charge beyond a power factor of 0.95 (common in UK and EU business tariffs), the energy charge and the I²R loss in a supply cable. Real tariffs vary.

  • Three-phase uses sequence a–b–c with Va at 0°. Nominal voltages from IEC 60038 (230/400 V) and ANSI C84.1 (120/208 V, 277/480 V).

Sources: Hughes, Electrical and Electronic Technology (AC chapters, three-phase and transformers); Boylestad, Introductory Circuit Analysis (phasors, resonance, power); Horowitz and Hill, The Art of Electronics (reactance, resonance and Q).

Runs entirely in your browser; nothing you type leaves this page.