AI cost and energy economics
What a token, a training run and a gigawatt datacenter cost: cost per million tokens, 6·N·D training cost, datacenter TCO against GPU life and power price, generation mix and overbuild, PPA prices and energy bills, embodied vs operational carbon, GPU depreciation, and an educational export-control and EU AI Act check.
Added
How to use it
Eight tabs, each a small calculator with the book’s worked example as a preset:
-
Cost per token — all-in $ per GPU-hour ÷ (tokens per second × 3,600) × 106, with a grid of prices and throughputs and, for reasoning models, the cost of one long answer.
-
Training cost — C ≈ 6·N·D, GPU-hours = C ÷ (dense peak × MFU × 3,600), times a $ range. Give the reported GPU-hours instead and it shows the MFU they imply.
-
Datacenter TCO — annual cost = hardware capex ÷ GPU life + energy (TWh × $/MWh) + facility overheads, as stacked bars for lives of two to eight years with the energy share on each, and a table at other power prices.
-
Generation mix — on-site turbine capacity (units × MW), the nameplate a source needs to supply an average load at its capacity factor, and the book’s menu of sources with time to power.
-
PPAs & bills — the price a power-purchase agreement implies (value ÷ MWh delivered) and a site’s annual energy bill across a price range, against the ≈ $80/MWh siting rule of thumb.
-
Embodied carbon — one accelerator’s manufacturing emissions against its running emissions on a chosen grid: the break-even time, the embodied share over its life, and a table across grids.
-
Depreciation — book value year by year on straight-line, double-declining or sum-of-digits schedules, comparing the life on the books with a shorter economic life.
-
Compliance (educational, not legal advice) — training compute against the EU AI Act’s 1025 FLOP presumption, and the US export-control Total Processing Performance (TPP) and performance density (PD) of an accelerator against the October 2023 ECCN 3A090 thresholds.
Numbers accept 1e9, 1,000 and 1_000.
Where the book’s figures differ
The tool computes; where the book prints a different number it says so on the tab.
-
Epoch’s 1 GW site: $30B of accelerators over five years is $6B a year, not $5B, so the annual total is $7.1B (with $0.6B of energy and $0.5B of facility), not "~$8B". Three years gives $11.1B; seven years $5.4B with energy at about 11%, not "past 20%". Depreciation is 10× energy.
-
Colossus: 35 turbines × 16.5 MW is 577.5 MW, not "roughly 400 MW".
-
TPP is the highest single-precision figure (2 × MacTOPS × bit length, dense), not a sum across precisions; non-datacenter parts at TPP ≥ 4,800 are NAC-eligible rather than licensed; and 3A090.b has a second band (TPP ≥ 1,600 with PD 3.2–5.92).
Limits
-
Every result is an estimate from simple formulas: no cost of capital, taxes, or utilisation ramps; straight-line depreciation in the TCO.
-
Throughput, MFU, prices and grid intensities are inputs, not predictions. Grid intensities are approximate yearly averages (Ember; EIA for the US). Hardware figures are dense (NVIDIA’s headline FP8/INT8 numbers assume 2:4 sparsity and are twice these).
-
The implied PPA price assumes full delivery for the whole term; Talen–AWS ramps to 1.92 GW by 2032, so its true average price is higher than the ≈ $63/MWh shown.
-
The compliance tab is a simplified, educational reading of ECCN 3A090 (October 2023, per CSET’s summary) and Article 51 of the EU AI Act. Later rules — the 2024 HBM controls, the rescinded 2025 diffusion rule, the April 2025 H20 licence requirement, case-by-case H200 licensing in 2026 — sit on top. It is not legal advice. Die areas for MI300X and B200 are estimates.
Sources
-
Accelerators (TPP table, as of 2026-10): NVIDIA H100, A100, L40S and DGX B200 pages; Hopper, Ampere and Ada architecture whitepapers (die areas, RTX 4090); AMD MI300X data sheet; SemiAnalysis on the H20 (Nov 2023).
-
CSET, "The Commerce Department’s October 2023 Export Control Update" — TPP, PD, the 3A090 thresholds.
-
Regulation (EU) 2024/1689, Article 51 — the 1025 FLOP presumption.
-
Epoch AI, "Total cost of ownership of a one-gigawatt AI data center".
-
Power Magazine on the $18B Talen–Amazon PPA (June 2025).
-
Meta, The Llama 3 Herd of Models — 405B parameters, 15.6T tokens, 30.84M H100 GPU-hours.
-
Embodied carbon of the H100 and HGX boards: Interact, "Understanding GPU’s Energy and Environmental Impact"; Green Software Foundation, SCI.
Related: AI hardware calculator (memory, roofline, training time and tokens per second — the throughput this tool prices), yield, chiplets and weights-in-silicon (what a good die costs), solar ROI (payback and LCOE of a single solar system).
Companion to The Economics: Cost per Token and the Depreciation Debate, the generation menu and the cost curve of the energy layer, Embodied versus operational carbon and AI Regulation and Export Controls of _AI Acceleration: From Transistors to Trillion-Parameter Models.
Linking to an example
Links can be written by hand. Add the tab after #: token, training, tco, power, energy,
carbon, depreciation or compliance. Settings not in the link take their defaults.
| Parameter | Meaning | Example |
|---|---|---|
|
All-in $ per GPU-hour (Cost per token) |
|
|
Output tokens per second per GPU |
|
|
Tokens per answer (optional) |
|
|
Parameters and training tokens, in billions (Training cost) |
|
|
GPU and precision: |
|
|
Dense peak TFLOPS |
|
|
Model FLOPs utilisation, % |
|
|
$ per GPU-hour range |
|
|
Reported GPU-hours, millions (0 = estimate from MFU) |
|
|
Hardware capex, $B (Datacenter TCO) |
|
|
GPU life, years |
|
|
Energy per year, TWh |
|
|
Power price, $/MWh |
|
|
Facility overheads, $B per year |
|
|
Turbines on site and MW each (Generation mix) |
|
|
Load in MW and duty cycle % |
|
|
Source: |
|
|
Capacity factor % |
|
|
PPA value $B, term in years, capacity GW, delivered load factor % (PPAs & bills) |
|
|
Site energy TWh per year and a low and high $/MWh |
|
|
Embodied kgCO2e per GPU (Embodied carbon) |
|
|
Board power W, utilisation %, PUE |
|
|
|
|
|
Grid intensity, gCO2e/kWh |
|
|
Service life, years |
|
|
Fleet capex, $B (Depreciation) |
|
|
Life on the books and economic life, years |
|
|
|
|
|
Salvage, % of cost |
|
|
Parameters and tokens in billions for the EU check (Compliance) |
|
|
Or total training FLOP (0 = use 6·N·D) |
|
|
|
|
|
Custom part: dense TOPS, bit length, logic-die mm², designed for datacenters ( |
|
|
One of the presets below; parameters given with it override the preset’s |
|
In a URL + means a space: write 1e25 or 1e%2B25. A hand-typed fl=1e+25 also works — the
tool reads 1e 25 back as 1e+25.
Presets:
example= |
Shows |
|---|---|
|
$3 per GPU-hour at 2,000 tokens/s ≈ $0.42 per million tokens (open) |
|
The same rate priced per 20,000-token reasoning answer (open) |
|
Llama 3.1 405B: 3.8 × 1025 FLOP, 30.84M H100-hours at $2–4 ≈ $62–123M, implied MFU ≈ 35% (open) |
|
The same run estimated at 20% MFU: twice the GPU-hours of 40% (open) |
|
$100B of accelerators on a 6-year schedule against a 3-year economic life (open) |
|
Epoch’s 1 GW site: $6B a year of depreciation, $7.1B in all (open) |
|
The same on a 3-year GPU life: $11.1B a year (open) |
|
A 7-year life: $5.4B a year, energy ≈ 11% (open) |
|
35 SMT-130 turbines × 16.5 MW = 577.5 MW (open) |
|
A 1 GW cluster at 80% duty needs ≈ 2.9 GW of solar at a 27.5% capacity factor (open) |
|
Talen–AWS: $18B over 17 years for 1.92 GW ≈ $63/MWh (open) |
|
8 TWh a year at $30–120/MWh = $240–960M (open) |
|
One H100, ~175 kgCO2e embodied, on a ~30 g/kWh hydro grid (open) |
|
The same card on the US-average grid (open) |
|
400B parameters × 4T tokens = 9.6 × 1024 FLOP, just under 1025 (open) |
|
Llama 3.1 405B at 3.8 × 1025 FLOP (open) |
|
H100: TPP 15,832, PD 19.4 — 3A090.a (open) |
|
H20: TPP 2,368, PD 2.9 — under the October 2023 lines (open) |
|
A800: TPP 4,992 — caught by the October 2023 rewrite (open) |